compressor — count_cycles (plc-tap)

A reciprocating or rotary-screw compressor with load/unload (or start/stop) capacity control already drives a relay contact — a load solenoid’s auxiliary contact or the starter contactor’s own auxiliary block — that closes once per load event, used today to drive a local run-light or hour-meter. This recipe passively taps that existing contact through an isolation relay or opto-isolated digital input; the edge box only ever reads a signal the compressor’s control already produces, and no Modbus/OPC write function code is ever issued (INV-4). The tapped contact closes for the duration of each load cycle and opens on unload, so the signal is a clean digital state rather than a narrow pulse. Compressor load/unload cycling is slow relative to any mechanical process inside the machine: a lightly-loaded reciprocating compressor can cycle as often as once every 20-30 s (roughly 0.03-0.05 Hz) under light, intermittent demand; sampling the digital input at 50 Hz gives >1000x margin over Nyquist for that rate while resolving contact bounce within a single transition.

  • Spec: dry-contact relay tap / isolated digital input, read-only
  • Signal: counter ({count}), range n/a
  • Allen-Bradley/Rockwell 700-HA33Z1 isolation relay (3PDT, ice-cube, DIN-rail) to buffer the tap
  • Omron G2RV-SR700 slim relay socket module for isolating the tapped contact
  • ifm electronic DI0005 opto-isolated digital input module for the edge box’s I/O channel

Install the isolation relay inside (or adjacent to) the compressor’s control panel, coil driven in parallel off the existing load solenoid auxiliary contact or starter contactor auxiliary block terminals; route the isolation relay’s isolated normally-open contact out to the edge box’s digital input. Never splice a new wire into the PLC’s or the starter’s own output terminal; tap only an already-present auxiliary contact.

24 VDC loop through the isolation relay’s dry contact to a digital input / counter channel on the edge box’s I/O module; keep the tap cable run separate from the compressor’s motor power and starter wiring to avoid induced noise and to keep the low-voltage tap physically isolated from line-voltage conductors.

observe and manually count 20 load/unload transitions over a normal demand period and compare the detector’s counter delta over the same window

Expected: counted load cycles exactly equal to the manual count (the tapped contact is the compressor’s own load-control event, so there is no demand-dependent slip)

  • de-energize and lock out the compressor control panel (LOTO) before opening it to wire the isolation relay, even though the tap itself only reads an existing signal
  • use an isolation relay (never a direct splice) so a wiring fault on the edge-box side can never back-feed voltage into the compressor’s starter or control circuit
  • be aware the compressor can auto-start on demand at any time even while the panel is open for wiring; confirm LOTO covers the starter circuit, not just the local disconnect

25–90 USD, difficulty 3/5, ~40 min install downtime.